Research master's thesisISSAT Sousse, LATIS laboratory (ENISO)Feb 2026 – presentsupervised by Mr. Faycel Jellali
Grid-forming control of a three-level T-type inverter
As inverter-based sources replace rotating machines, microgrids lose the inertia that used to hold their voltage and frequency. My thesis asks whether droop control with filtered powers lets a 10 kVA, 400 V three-level T-type inverter, connected through an LCL filter, form a clean voltage on its own, couple smoothly to a weak grid (short-circuit ratio 3) and stay stable through setpoint changes and grid disturbances.
- Full control chain in MATLAB/Simulink, sampled at 25 µs: P–ω / Q–V droop equivalent to a virtual synchronous machine (H ≈ 0.8 s), cascaded PI voltage and current loops in the dq frame, three-level SVPWM at 40 kHz with neutral-point balancing.
- Pre-synchronisation and synchrocheck for grid coupling, and three protections: a 30 A current limiter, a threshold-based virtual impedance and a ±9.5 kW active-power limiter.
- 21 simulation test cases, all run with the final control: islanded, coupling and islanding, grid-connected.
- Synchronism kept without a PLL through 20° and 60° phase jumps and 150 ms three-phase and single-phase faults; unintentional islanding ridden through without a mode change.
1.8 %voltage THD in islanded mode (1.0 % for current)
±8.7°phase error at breaker closing, coupling current below 80 % of rated peak
< 0.2 sfor active power to reach its setpoint, with no overshoot
1.1 %at the coupling point for a 10 % grid voltage sag
Results from simulation only, with an ideal DC bus and lossless switches; the thesis sets out the limits and the path to hardware-in-the-loop and a reduced-power prototype.
MATLAB / SimulinkGrid-formingDroop controlVirtual synchronous machinedq control3-level SVPWMLCL filterFault ride-through